Model catalogue reference: 93E-100/100
UPS topology: Double conversion, IGBT converters
UPS dimensions (width x depth x height) mm3: 600 x 800 x 1880 mm
Weight (kg) without batteries: 283
Weight with internal batteries (kg): Bottom / rear
UPS colour: Black, RAL 9005
Rated output power: 100kVA/90kW
Battery technology: 12 V, VRLA
Battery design life: 5 or 10 years
Battery quantity: 36 blocks, 216 cells per battery string or
38 blocks, 228 cells per battery string or
40 blocks, 240 cells per battery string (default)
Battery voltage: 432 V (216 Cells) or 456 V (228 Cells) or 480 V (240 Cells, Default)
Recharge time to 90 % capacity: Maximum 10 hours recommended (dependent on battery size)
Recharge profile: Advanced Battery Management (ABM) = 90% resting,10% floating/charging (typical)
End of discharge voltage: 216 Cells = 1.8V/Cell, 228 Cells = 1.73V/Cell, 240 Cells = 1.67V/Cell
Charging current (at full load): 40 A